IntesisBox
®
Modbus Server - Mitsubishi Electric G50 datasheet v10 r11 eng
TRADEMARKS: All trademarks and tradenames used in this document are acknowledged to be the copyright of their respective holders.
Modbus interface
General
Max. Number of
Mitsubishi Elec.G50s
Up to 4 G50s can be supported. There are four different models for this gateway,
supporting: 1, 2, 3 or 4 G50s respectively.
Virtual signals
One communication error virtual signal per every G50 device defined.
One communication error virtual signal per every group into the G50 device.
One virtual signal per every group into the G50 device to enable/disable this
group in the polling process.
All these virtual signals can be read/written from Modbus.
Modbus interface
Device type Slave.
Modbus modes
supported
TCP, RTU RS232 or RS485.
Modbus TCP
configuration
parameters
IP address.
Subnet mask.
Default gateway address.
TCP port.
Modbus RTU
configuration
parameters
RS232/RS485.
Baud rate.
Slave number.
Points
Configuration
No point configuration needs to be done, all the Mitsubishi Electric G50
signals are automatically associated to predefined fixed Modbus Addresses.
Modbus function
codes supported
Read functions:
3- Read holding registers.
4- Read input registers.
Write functions:
6- Write single register.
16- Write multiple registers.
If poll records are used to read/write multiple records, the range of addresses requested must contain
valid addresses, if not the corresponding Modbus error code will be responded.
Modbus data coding
All the point's values are coded in 2 bytes registers (even if their possible values
are 0 and 1) and expressed in MSB..LSB.