6 - 23
6 INSPECTION AND MAINTENANCE
(f) Flowchart for when "BT " displays on 7-segment LED
"BT1" or "BT2" displays when the battery voltage is lowered.
"BT1" or "BT2" displays at the following cases.
• BT1: Battery voltage 2.7V or less
• BT2: Battery voltage 2.5V or less
The following shows the flowchart for when "BT1" or "BT2" displays on
7-segment LED.
A hardware fault
Explain the error symptom and get
advice from our sales representative.
END
YES (SM58, SM51 OFF)
NO (SM58 or SM51 ON)
Replace the battery.
"BT " displays on 7-segment LED
Turn off the Multiple CPU system
power supply.
Turn on the Multiple CPU system
power supply.
Does "BT "
disappear on 7-segment
LED (Confirm ON/OFF by
monitoring SM )
REMARK
If SM51, SM58 turns on, the contents of the programs, parameters, motion device(#),
latch range device and absolute position data cannot be guaranteed.
It is recommended to back-up the data periodically.