Mitsubishi RS232/485/LAN Serial Communication Control Instrukcja Obsługi

Przeglądaj online lub pobierz Instrukcja Obsługi dla Networking Mitsubishi RS232/485/LAN Serial Communication Control. Mitsubishi RS232/485/LAN Serial Communication Control Hardware manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 349
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 0
2-1
Chap.2
Chapter 2 Connection to a PLC
1 IDEC ........................................................................................................2-14
1.1 Connection Table ....................................................................................................... 2-14
1.1.1 Compatible PLCs ................................................................................................ 2-14
1.2 System Configuration................................................................................................ 2-17
1.2.1 FA Series (using the Serial Interface unit) .......................................................2-17
1.2.2 FA Series (using the Link Adapter) ................................................................... 2-17
1.2.3 MICRO3 (connects to CPU Unit loader port) ...................................................2-18
1.2.4 MICRO3C (connects to CPU Unit loader port)................................................. 2-18
1.2.5 MICRO3C (connects from the CPU to the Data Link port) ............................. 2-18
1.2.6 OpenNet Controller (connects to RS-232C port of the CPU unit) ...................2-19
1.2.7 OpenNet Controller (connects to RS-485 port of the CPU unit)...................... 2-19
1.2.8 MicroSmart/MICROSmart Pentra (uses the communication port1)............... 2-20
1.2.9 MicroSmart/MICROSmart Pentra (uses the communication port 2).............. 2-21
1.2.10 MicroSmart/MICROSmart Pentra (uses the Communication Module)........ 2-23
1.2.11 OpenNet Controller/MICROSmart/MICROSmart Pentra ( uses Web Server
Unit ).............................................................................................................................2-24
1.2.12 1: N Communication-OpenNet Controller/MICROSmart/MICROSmart Pentra
.......................................................................................................................................2-25
1.3 Connection Diagram..................................................................................................2-26
Connection Diagram 1-1: FA-3S (PF3S-SIF2) to MICRO/I.......................................2-26
Connection Diagram 1-2: FA-3S (PF3S-SIF4) to MICRO/I.......................................2-27
Connection Diagram 1-3: FA-3S, FA-2J (PF2-CLA) to MICRO/I..............................2-28
Connection Diagram 1-4: MICRO3 (loader port) to MICRO/I .................................. 2-29
Connection Diagram 1-5: MICRO3C (Loader port) to MICRO/I OpenNet Controller
(RS-232C port) to MICRO/I MICROSmart/MICROSmart Pentra (RS-232C port) to
MICRO/I ....................................................................................................................... 2-30
Connection Diagram 1-6: MICRO3C (Data Link port) to MICRO/I OpenNet
Controller (RS-485 port) to MICRO/I MICROSmart/MICROSmart Pentra (RS-485
port) to MICRO/I.......................................................................................................... 2-31
Connection Diagram 1-7: MICROSmart/MICROSmart Pentra (RS-232C Port 1) to
MICRO/I ....................................................................................................................... 2-32
Connection Diagram 1-8: MICROSmart/MICROSmart Pentra (FC5A-SIF2) to
Przeglądanie stron 0
1 2 3 4 5 6 ... 348 349

Podsumowanie treści

Strona 1

2-1 Chap.2Chapter 2 Connection to a PLC 1 IDEC ...

Strona 2

Chapter 2 Connection to a PLC 2-10 14.2.1 MP920, MP930 (connects to CPU Unit RS-232C port) ...2-271 14.2.2 MP920,MP930

Strona 3

Chapter 2 Connection to a PLC 2-100 Connection Diagram 3-8: RS-422 Adaptor to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No.

Strona 4

3 Omron 2-101 Chap.23.4 Environment Settings 3.4.1 PLC Link Unit Settings Perform the settings using the rotary switches and DIP switches on the

Strona 5

Chapter 2 Connection to a PLC 2-102 3.4.2 CPU Unit RS-232C Link I/F Settings Write the RS-232C I/F setting items for the System Settings Area using

Strona 6

3 Omron 2-103 Chap.23.4.3 CPU Unit RS-232C Link I/F Settings (CS1 Series) Write the RS-232C I/F setting items for the System Settings Area using

Strona 7

Chapter 2 Connection to a PLC 2-104 3.4.4 C200Hα (Communication Board) Settings Write the Communication Board setting items for the System Setting

Strona 8

3 Omron 2-105 Chap.23.4.5 CS1 Series (Communication Board) Settings Write the Communication Board setting items for the System Settings Area usi

Strona 9

Chapter 2 Connection to a PLC 2-106 3.4.6 CPU Direct Settings (CPM1/CPM1A/CPM2A) Connect via CPM-CIF01 ( RS232C)/CPM 1-CIF11 ( RS422). Setting Ite

Strona 10

3 Omron 2-107 Chap.23.5 Usable Devices 3.5.1 SYSMAC-C (when the PLC type setting is SYSMAC C Series) ・ Bit Device Device Symbol Device Name HG

Strona 11

Chapter 2 Connection to a PLC 2-108 3.5.2 CS1 Series (when the PLC type setting is SYSMAC CS1 Series) ・ Bit Device Device Symbol Device Name HG

Strona 12

3 Omron 2-109 Chap.2・ Word Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Core I/O WCIO CIO 0 - 6143

Strona 13

2-11 Chap.216 FANUC ...2-295 16.1 Connection Table

Strona 14 - 1.1.1 Compatible PLCs

Chapter2 Connection to a PLC 2-110 4 Allen-Bradley PLCs 4.1 Connection Table 4.1.1 Compatible PLCs WindO/I-NV2 Setting Name Manufacturer Series Nam

Strona 15 - 2-15

4 Allen-Bradley PLCs 2-111 Chap.2Selecting DirectLogic Logix DF1(Full Duplex) or DirectLogic(Ethernet) for the Host I/F Driver allows the user t

Strona 16

Chapter2 Connection to a PLC 2-112 WindO/I-NV2 Setting NameManufacturer Series Name System (CPU unit) Link unit Interface Host I/F DriverControlLog

Strona 17 - 1.2 System Configuration

4 Allen-Bradley PLCs 2-113 Chap.24.2 System Configuration This is the system configuration to connect Allen-Bradley PLCs to MICRO/I. 4.2.1 SLC 5

Strona 18

Chapter2 Connection to a PLC 2-114 4.2.4 MicroLogix 1000/1100/1200/1500 (Mini Din connector on CPU Unit) RS-232C (Connection Diagram 4-5)MicroL

Strona 19 - 2-19

4 Allen-Bradley PLCs 2-115 Chap.24.2.6 Ethernet/IP (MicroLogix, PLC-5, SLC 500, ControlLogix, CompactLogix) ControlLogix +1756-ENBT CompactLogi

Strona 20

Chapter2 Connection to a PLC 2-116 4.3 Connection Diagram For details regarding wiring and termination resistors, refer to "3 Important Poin

Strona 21 - 2-21

4 Allen-Bradley PLCs 2-117 Chap.2Connection Diagram 4-2: Interface Module (RS-232C) to MICRO/I and PLC-5 (RS-232-C) to MICRO/I PLC(RS-232C)

Strona 22 - (part number: HG9Z-XC183)

Chapter2 Connection to a PLC 2-118 Connection Diagram 4-4: PLC-5 (RS-422) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. P

Strona 23 - 2-23

4 Allen-Bradley PLCs 2-119 Chap.2Connection Diagram 4-5: MicroLogix 1000/1200/1500(Mini Din connector) to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/

Strona 24 - Server Unit )

Chapter 2 Connection to a PLC 2-12 19 FUJI ... 2-3

Strona 25 - 2-25

Chapter2 Connection to a PLC 2-120 Connection Diagram 4-7: ControlLogix/CompactLogix/FlexLogix - MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C)

Strona 26 - 1.3 Connection Diagram

4 Allen-Bradley PLCs 2-121 Chap.24.4 Environment Settings Allowed communication settings for MicroLogix, SLC 500 and PLC-5 are as follows. 4.4.1

Strona 27 - 2-27

Chapter2 Connection to a PLC 2-122 4.4.2 SLC 500 (Half Duplex) Item Setting Communication Interface RS-232C Baud Rate (bps) (*1)(*2) 1200, 2400,

Strona 28

4 Allen-Bradley PLCs 2-123 Chap.24.4.3 PLC-5 Item Setting Communication Interface(*1)(*2) RS-232-C/RS-485-A (4 line) Baud Rate (bps) (*4)(*5)

Strona 29 - 2-29

Chapter2 Connection to a PLC 2-124 4.4.4 Ethernet/IP (ControlLogix, CompactLogix, PLC-5, SLC 500, MicroLogix ) Communication Interface Setting (Et

Strona 30

4 Allen-Bradley PLCs 2-125 Chap.24.4.5 ControlLogix, CompactLogix, FlexLogix Item Setting Baud Rate (bps) (*1) 1200, 2400, 4800, 9600, 19200 D

Strona 31

Chapter2 Connection to a PLC 2-126 4.5 Compatible Devices The types of compatible devices and their ranges are shown below. Device address selectio

Strona 32

4 Allen-Bradley PLCs 2-127 Chap.24.5.1 MicroLogix, SLC 500 (Full Duplex) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Wri

Strona 33

Chapter2 Connection to a PLC 2-128 (*1)Address selection rule is as follows. Standard device address format of WindO/I-NV2 I 1625515 Example

Strona 34 - 1.4 Environment Settings

4 Allen-Bradley PLCs 2-129 Chap.2(*3)Address selection rule is as follows. Standard device address format of WindO/I-NV2 TEN 255255 Example

Strona 35 - 1.4.3 MICRO

2-13 Chap.2Connection Diagram 20-1: RS-485 D-sub 15P - MICRO/I ...2-336 Connection Diagram 20-2: RS-232 D-sub 9P

Strona 36

Chapter2 Connection to a PLC 2-130 ・ Word Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Output WO O 0 - 1625

Strona 37 - 1.5 Usable Devices

4 Allen-Bradley PLCs 2-131 Chap.2(*1)Address selection rule is as follows. Standard device address format of WindO/I-NV2 I 16255 Example

Strona 38 - 1.5.2 FA-3S (CP12, CP13)

Chapter2 Connection to a PLC 2-132 (*3)Address selection rule is as follows. WindO/I-NV2 uses 32 bit device as the divided 2 word device. Therefore

Strona 39 - 1.5.3 MICRO

4 Allen-Bradley PLCs 2-133 Chap.24.5.2 SLC 500 (Half Duplex) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address

Strona 40

Chapter2 Connection to a PLC 2-134 ・ Word Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Input WI I 0 - 301 R

Strona 41 - 2 Mitsubishi

4 Allen-Bradley PLCs 2-135 Chap.2(*2) Address selection rule is as follows. Standard device address format of WindO/I-NV2 N 255255 Example

Strona 42

Chapter2 Connection to a PLC 2-136 4.5.3 PLC-5 (Half Duplex) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradua

Strona 43 - 2-43

4 Allen-Bradley PLCs 2-137 Chap.2(*2) Address selection rule is as follows. Standard device address format of WindO/I-NV2 B 00301215 Example

Strona 44

Chapter2 Connection to a PLC 2-138 ・ Word Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Input WI I 0 - 277

Strona 45 - 2-45

4 Allen-Bradley PLCs 2-139 Chap.2(*2) Address selection rule is as follows. Standard device address format of WindO/I-NV2 N 040045 Example PLC

Strona 46

Chapter 2 Connection to a PLC 2-14 1 IDEC Selecting MICRO3/MICRO3C or OpenNet(FC3A),MicroSmart(FC4A/FC5A) as the Host I/F Driver allows the user to

Strona 47 - 2-47

Chapter2 Connection to a PLC 2-140 4.5.4 Ethernet/IP If you select Ethernet/IP as Host I/F driver, the driver contains some PLCs devices. Therefore

Strona 48 - Q2ASCPU

4 Allen-Bradley PLCs 2-141 Chap.2(*1) Address selection rule is as follows. Standard device address format of WindO/I-NV2 I 1625515 Example

Strona 49 - 2-49

Chapter2 Connection to a PLC 2-142 (*3) Address selection rule is as follows. Standard device address format of WindO/I-NV2 B 25525515 Example

Strona 50 - (part number: HG9Z-XC245)

4 Allen-Bradley PLCs 2-143 Chap.2・ Word Device Device SymbolDevice Name HG PLCAddress Range Read /Write Address GradualSLC/MicroLogix Input (W

Strona 51 - 2-51

Chapter2 Connection to a PLC 2-144 (*1) Address selection rule is as follows. Standard device address format of WindO/I-NV2 I 16255 Example Micr

Strona 52 - FX2N + FX2N-CNV-BD

4 Allen-Bradley PLCs 2-145 Chap.2(*3) Address selection rule is as follows. Standard device address format of WindO/I-NV2 WB 255255 Example M

Strona 53 - 2-53

Chapter2 Connection to a PLC 2-146 Cross reference table of devices name Bit Device Device Name Device Symbol MicroLogix/SLC500 PLC-5 ControlLogi

Strona 54 - 2.3 Connection Diagram

4 Allen-Bradley PLCs 2-147 Chap.2Control Unload Bit RUL Control Unload Bit - - Control Running Bit RIN Control Running Bit - - Control Found

Strona 55

Chapter2 Connection to a PLC 2-148 Word Device Device Name Device Symbol MicroLogix/SLC500 PLC-5 ControlLogix CompactLogix SLC/MicroLogix Input (

Strona 56

4 Allen-Bradley PLCs 2-149 Chap.24.5.4 Logix DF1 (Full Duplex) Word Device Device SymbolDevice Name HG PLCAddress Range Read /Write Address Gra

Strona 57 - 2-57

1 IDEC 2-15 Chap.2WindO/I-NV2 Setting Name Manu facturer Series Name System (CPU unit) Link unit Interface Flow Control Host I/F Driver RS-232C

Strona 58

Chapter2 Connection to a PLC 2-150 (*2) Address selection rule is as follows. WindO/I-NV2 uses 32 bit device as the divided 2 word device. Therefor

Strona 59 - 2-59

4 Allen-Bradley PLCs 2-151 Chap.24.6 The way to set device address when use ControlLogix, CompactLogix series In ControlLogix and CompactLogix s

Strona 60 - MICRO/I to

Chapter2 Connection to a PLC 2-152 4.6.3 The process to select device address 1. Define some tags in RSLogix 5000 software. Tag name Type Array

Strona 61 - Shield Wire

4 Allen-Bradley PLCs 2-153 Chap.24.6.4 Setting Example for WindO/I-NV2 Refer to the following about setting example for WindO/I-NV2 software.

Strona 62

Chapter2 Connection to a PLC 2-154 5 SIEMENS 5.1 Connection Table 5.1.1 Compatible PLCs WindO/I-NV2 Setting Name ManufacturerSeries Name System (CP

Strona 63 - 2.4 Environment Settings

5 SIEMENS 2-155 Chap.25.2 System Configuration The following document explains the connection of SIEMENS PLCs to MICRO/I screens. 5.2.1 S7-200

Strona 64

Chapter2 Connection to a PLC 2-156 5.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cable

Strona 65 - 2-65

5 SIEMENS 2-157 Chap.2Connection Diagram 5-2: S7-300/S7-400 (RS-232C) to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No. N

Strona 66 - 2.4.6 MELSEC-FX Series

Chapter2 Connection to a PLC 2-158 5.4 Environment Settings 5.4.1 S7-200 The communication port settings for S7-200 and MICRO/I host port are as fo

Strona 67 - MELSEC-Q/QnA

5 SIEMENS 2-159 Chap.25.4.2 S7-300/S7-400 The communication port settings for S7-300 and MICRO/I host port are as follows. Items Details Seria

Strona 68

Chapter 2 Connection to a PLC 2-16 WindO/I-NV2 Setting Name Manu facturer Series Name System (CPU unit) Link unit Interface Flow Control Host I/F D

Strona 69 - 2.5.1 MELSEC-AnA (LINK)

Chapter2 Connection to a PLC 2-160 5.5 Usable Devices 5.5.1 S7-200 ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress

Strona 70 - 2.5.1 MELSEC-AnN (LINK)

5 SIEMENS 2-161 Chap.2 - The devices (V, I, Q, M, SM, S) which include a period in the address in S7-200 are written without a period in MICR

Strona 71 - 2.5.2 MELSEC-AnA (CPU)

Chapter2 Connection to a PLC 2-162 5.5.2 S7-300/S7-400 When using CP-341/441, following devices can be read and written. When using CP-340440, only

Strona 72 - 2.5.3 MELSEC-AnN (CPU)

6 Keyence 2-163 Chap.26 Keyence 6.1 Connection Table 6.1.1 Compatible PLCs WindO/I-NV2 Setting Name Manufacturer Series NameSystem (CPU unit) Li

Strona 73 - 2.5.4 MELSEC-AnU (CPU)

Chapter2 Connection to a PLC 2-164 6.2 System Configuration This is the system configuration for connection of Keyence PLCs to the MICRO/I. 6.2.1

Strona 74 - 2.5.5 MELSEC-A1S/A2C (CPU)

6 Keyence 2-165 Chap.26.2.4 Connection to the CPU unit modular connector for KV/KZ series RS-232CKV Series Connection Diagram 6-1 MICRO/IABC 01

Strona 75 - 2-75

Chapter2 Connection to a PLC 2-166 6.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cable

Strona 76 - 2.5.6 MELSEC-Q/QnA(Link)

6 Keyence 2-167 Chap.2Connection Diagram 6-2:KV-700/1000 + KV-20R(PORT1) to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No

Strona 77 - 2-77

Chapter2 Connection to a PLC 2-168 Connection Diagram 6-4: KV-700/1000 + KV-20R (PORT2-RS-422A/485-4wire) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/

Strona 78 - 2.5.7 MELSEC-Q (CPU)

6 Keyence 2-169 Chap.2Connection Diagram 6-5: KV-700/1000 + KV-20R (PORT2-RS-485-2wire) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/42

Strona 79 - 2-79

1 IDEC 2-17 Chap.21.2 System Configuration This is the system configuration for connection of IDEC PLCs to the MICRO/I. 1.2.1 FA Series (using t

Strona 80 - 2.5.8 MELSEC-FX (CPU)

Chapter2 Connection to a PLC 2-170 6.4 Environment Settings 6.4.1 KV-700/1000, Conventional KV Series Item Setting Communication Device Number RS

Strona 81 - 2.5.9 MELSEC-FX2N (CPU)

6 Keyence 2-171 Chap.26.4.3 Environment settings for connection to the KV-700/1000 + KV-20R Item Setting Transmission method RS-232C, RS-422/

Strona 82 - 2.5.10 MELSEC-FX3UC (CPU)

Chapter2 Connection to a PLC 2-172 6.5 Usable Devices 6.5.1 KV-700/1000 ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAdd

Strona 83

6 Keyence 2-173 Chap.2・ Word Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Timer (Preset) TS T 0 - 3999

Strona 84 - Word device

Chapter2 Connection to a PLC 2-174 6.5.2 Visual KV/Conventional KV Series ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/Write

Strona 85 - 3 Omron

7.SHARP 2-175 Chap.2 7.SHARP 7.1 Connection Table 7.1.1 Compatible PLCs WindO/I-NV2 Setting Name ManufacturerSeries Name System (CPU unit) Link

Strona 86

Chapter2 Connection to a PLC 2-176 7.2 System Configuration This is the system configuration for connection of SHARP PLCs to the MICRO/I. 7.2.1 JW

Strona 87 - 2-87

7.SHARP 2-177 Chap.27.2.3 JW50/70/100 Series (using communication port) RS-232C Connection Diagram 7-3 JW-22CU JW-70CU/CUH JW-100CU/CUH MICRO

Strona 88 - (part number: HG9Z-XC155)

Chapter2 Connection to a PLC 2-178 7.2.6 JW10 Series RS-422 MMI Connection Diagram 7-6 JW-10 MICRO/IRS-485(2-wire) Connection Diagram 7-7

Strona 89 - 2-89

7.SHARP 2-179 Chap.27.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cable. For detail

Strona 90

Chapter 2 Connection to a PLC 2-18 1.2.3 MICRO3 (connects to CPU Unit loader port) MICRO3 interface FC2A-C10 /C16 /C24 MICRO/I Connection Diagra

Strona 91 - 2-91

Chapter2 Connection to a PLC 2-180 Connection Diagram 7-2: RS-485 Link Unit to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No.

Strona 92 - C200HS-CPU21/23/31/33

7.SHARP 2-181 Chap.2Connection Diagram 7-3: PLC(RS-232C) Communication Port to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin

Strona 93 - Diagram 3-7

Chapter2 Connection to a PLC 2-182 Connection Diagram 7-5: PLC(RS-485) Communication Port to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/4

Strona 94 - 3.3 Connection Diagram

7.SHARP 2-183 Chap.2Connection Diagram 7-6: JW-10 MMI Port(RS-422) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pin

Strona 95 - 2-95

Chapter2 Connection to a PLC 2-184 Connection Diagram 7-7: JW-10 Communication Port (RS-485) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-48

Strona 96

7.SHARP 2-185 Chap.27.4 Environment Settings 7.4.1 Using Computer Link Module Item Setting Communication Method RS-485-2 wires (Set DIP switch

Strona 97 - 2-97

Chapter2 Connection to a PLC 2-186 7.4.2 Using Communication Port Item Setting Communication Method RS-232C RS-485(422) Station No. 001 to 037

Strona 98

7.SHARP 2-187 Chap.27.5 Usable Devices The types of devices handles by the MICRO/I and their ranges are shown below. Bit Device WindO/I-NV2 Devi

Strona 99 - 2-99

Chapter2 Connection to a PLC 2-188 Word Device WindO/I-NV2 Device Name R/W WindO/I-NV2 address PLC Device Name PLC address Timer(Current Value) R

Strona 100 - Connector

8 Hitachi 2-189 Chap.28 Hitachi 8.1 Supported Programmable Logic Controllers WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit

Strona 101 - 3.4.1 PLC Link Unit Settings

1 IDEC 2-19 Chap.21.2.6 OpenNet Controller (connects to RS-232C port of the CPU unit) OpenNet Controller interface FC3A-CP2 MICRO/I Connectio

Strona 102 - Item Setting

Chapter 2 Connection to a PLC 2-190 8.2 System Configuration This is the system configuration for connection of Hitachi PLC to the MICRO/I. 8.2.1

Strona 103 - Channel Item Setting

8 Hitachi 2-191 Chap.28.2.3 S10V RS-232C Port on CPU Unit 接続図 8-2 RS-232C S10V LQP510 MICRO/I 8.2.4 S10V RS-422 Port on CPU Unit 接続図 8-3 RS-4

Strona 104 - 3.4.4 C200H

Chapter 2 Connection to a PLC 2-192 8.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cabl

Strona 105 - Port 1 Port 2

8 Hitachi 2-193 Chap.2Connection Diagram 8-2: S10mini ( RS-232C ) to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No. Name

Strona 106 - RS-232C

Chapter 2 Connection to a PLC 2-194 8.4 Environment Settings 8.4.1 S10mini, S10V Item Setting Serial Interface RS-232C , RS-485(422) 4wires Baud

Strona 107 - 3.5 Usable Devices

8 Hitachi 2-195 Chap.28.5 Usable Devices ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Input Relay

Strona 108 - ・ Bit Device

Chapter 2 Connection to a PLC 2-196 ・ Word Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Input Relay XW X 0 -

Strona 109 - 2-109

8 Hitachi 2-197 Chap.2

Strona 110 - 4 Allen-Bradley PLCs

Chapter2 Connection to a PLC 2-198 9 JTEKT(Toyoda) 9.1 Connection Table 9.1.1 Compatible PLCs WindO/I-NV2 Setting Name Manufacturer Series Name Sy

Strona 111

9 JTEKT(Toyoda) 2-199 Chap.29.2 System Configuration This is the system configuration for connection of JTEKT(Toyoda) PLCs to the MICRO/I. 9.2.

Strona 112 - Host I/F Driver

Chapter 2 Connection to a PLC 2-2 MICRO/I ...

Strona 113 - 4.2.3 PLC-5 (CPU Direct)

Chapter 2 Connection to a PLC 2-20 1.2.8 MicroSmart/MICROSmart Pentra (uses the communication port1) MICRO/IRS-232C FC4A FC5A Connection Diagram1-

Strona 114

Chapter2 Connection to a PLC 2-200 9.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cable

Strona 115 - + 1761-NET-ENI

9 JTEKT(Toyoda) 2-201 Chap.2Connection Diagram 9-2: TOYOPUC-PC3JG (Built-in Link) - MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) P

Strona 116 - 4.3 Connection Diagram

Chapter2 Connection to a PLC 2-202 9.4 Environment Settings 9.4.1 TOYOPUC-PC3J Series Item Setting Interface RS485(422)-2 Station No. 0-37 [set

Strona 117 - PLC-5 (RS-232-C) to MICRO/I

9 JTEKT(Toyoda) 2-203 Chap.29.5 Usable Devices 9.5.1 TOYOPUC-PC3J ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Addr

Strona 118

Chapter2 Connection to a PLC 2-204 Counter contact P1C C 0 - 1FF R Extended input EX EX 0 - 7FF R/W Extended output EY EY 0 - 7FF R/W

Strona 119 - MICRO/I

9 JTEKT(Toyoda) 2-205 Chap.2Link relay P3WL L 0 - 7F R/W Timer contact P3WT T 0 - 1F R Counter contact P3WC C 0 - 1F R Present va

Strona 120 - MICRO/I

Chapter2 Connection to a PLC 2-206 Extended counter contact WEC EC 0 - 7F R (*1) Extended present value register EN EN 0 - 7FF R Extended d

Strona 121 - 4.4 Environment Settings

10 Toshiba Machine Works 2-207 Chap.210 Toshiba Machine Works 10.1 Connection Table 10.1.1 Compatible PLCs WindO/I-NV2 Setting Name Manufacture

Strona 122 - 4.4.2 SLC 500 (Half Duplex)

Chapter2 Connection to a PLC 2-208 10.2 System Configuration This is the system configuration for connection of Toshiba machine works PLCs to the M

Strona 123 - 4.4.3 PLC-5

10 Toshiba Machine Works 2-209 Chap.210.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not th

Strona 124 - « Logix ».)

1 IDEC 2-21 Chap.21.2.9 MicroSmart/MICROSmart Pentra (uses the communication port 2) FC4A-C16R2 /-C24R2RS-232C MICRO/I FC4A-

Strona 125

Chapter2 Connection to a PLC 2-210 Connection Diagram 10-3:TCmini (RS-485) - MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pi

Strona 126 - 4.5 Compatible Devices

10 Toshiba Machine Works 2-211 Chap.210.4 Environment Settings 10.4.1 TC200 Items Details Serial Interface RS-232C PC No. 00 - 63 (Set same a

Strona 127 - 2-127

Chapter2 Connection to a PLC 2-212 10.5 Usable Devices ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Inpu

Strona 128

11 GE Fanuc Automation 2-213 Chap.211 GE Fanuc Automation 11.1 Connection Table 11.1.1 Compatible PLCs WindO/I-NV2 Setting Name Manufacturer Se

Strona 129 - 2-129

Chapter2 Connection to a PLC 2-214 11.2 System Configuration The following document explains the connection of GE Fanuc PLCs to MICRO/I screens. 1

Strona 130 - ・ Word Device

11 GE Fanuc Automation 2-215 Chap.211.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not for t

Strona 131 - 123:255

Chapter2 Connection to a PLC 2-216 Connection Diagram 11-2: Series 90-30 Communication Coprocessor Module (CMM) (RS-422(485)) to MICRO/I PLC(RS-48

Strona 132 - 1232550 and F1232551

11 GE Fanuc Automation 2-217 Chap.2Connection Diagram 11-3: PLC(RS-485) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No.

Strona 133 - 4.5.2 SLC 500 (Half Duplex)

Chapter2 Connection to a PLC 2-218 Connection Diagram 11-4 PLC(RS-232C) to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No. Na

Strona 134

11 GE Fanuc Automation 2-219 Chap.211.4 Environment Settings The communication port settings for GE Fanuc PLCs and MICRO/I host port are as foll

Strona 135 - 2-135

Chapter 2 Connection to a PLC 2-22 FC4A-D***** FC5A-D***** FC4A-PC1 (Communication Adapter) RS-232C MICRO/I FC4A-HPH1 (HMI Base Module)FC4A-PC3 (C

Strona 136 - 4.5.3 PLC-5 (Half Duplex)

Chapter2 Connection to a PLC 2-220 11.4.3 VersaMax Micro/Nano Item Setting Interface RS-232C ( Port 1 ) RS-485-4wires( Port 2 ) Baud Rate [bps

Strona 137 - :12 / TD

11 GE Fanuc Automation 2-221 Chap.211.5 Usable Devices The types of devices supported by the MICRO/I and their ranges are shown below. ・ Bit D

Strona 138

Chapter2 Connection to a PLC 2-222 ・ Word Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Discrete Inputs WI %I

Strona 139 - 2-139

12 Modbus 2-223 Chap.212 Modbus Selecting Modbus RTU or MODBUS/TCP Client for the Host I/F Driver allows the user to use the 1: N Communication

Strona 140 - 4.5.4 Ethernet/IP

Chapter2 Connection to a PLC 2-224 12.1.2 Compatible PLCs WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit Interface

Strona 141 - :277/17

12 Modbus 2-225 Chap.2WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit Interface Flow Control Host I/F Driver Not r

Strona 142 - 12:123/EN

Chapter2 Connection to a PLC 2-226 WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit Interface Flow Control Host I/F Dr

Strona 143 - 2-143

12 Modbus 2-227 Chap.212.2 System Configuration This is the system configuration for connection of Schneider PLCs to the MICRO/I. 12.2.1 Modbus

Strona 144

Chapter2 Connection to a PLC 2-228 12.2.4 Twido Serial Port on CPU module MICRO/IRS-485 Connection Diagram 12-2TWD LC*A 10DRF TWD LC*A 16DRF TWD

Strona 145 - 1232550 or F1232551

12 Modbus 2-229 Chap.2Compact Controller + Communication Adapter TWD LC*A 16DRF TWD LC*A 24DRF TWD LCA* 40DRF RS-23

Strona 146 - Bit Device

1 IDEC 2-23 Chap.21.2.10 MicroSmart/MICROSmart Pentra (uses the Communication Module) FC4A-D***** FC5A-D***** RS-232C MICRO/I FC4A-HPC1 FC4A-D**

Strona 147 - 2-147

Chapter2 Connection to a PLC 2-230 Module Controller + Communication Module MICRO/I RS-232C Connection Diagram 12-1TWD NOZ232D MICRO/I RS-485 Co

Strona 148 - Word Device

12 Modbus 2-231 Chap.2Module Controller + HMI Module + Communication Adapter MICRO/I TWD LMDA 20DTK TWD LMDA 20DUK TWD LMDA 20DRT TWD LMDA 40DT

Strona 149 - 2-149

Chapter2 Connection to a PLC 2-232 12.2.5 Momentum (MODUBS/TCP Client) HG3F/4F Ethernet 10BASE-T171CCC9602 - Use the direct connection with the

Strona 150

12 Modbus 2-233 Chap.212.2.7 1: N Communication- TWDLCAA16DRF/TWDLCAA24DRF +TWDNAC485T (Communication board) The 1: N communication can be estab

Strona 151 - 4.6.1 The way of mapping

Chapter2 Connection to a PLC 2-234 12.3 Connection Diagram For details regarding wiring and termination resistors, refer to "3 Important Po

Strona 152

12 Modbus 2-235 Chap.2Connection Diagram 12-2: TWDNAC485D to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pin No. Name

Strona 153

Chapter2 Connection to a PLC 2-236 Connection Diagram 12-3: TWDNAC485T to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pin

Strona 154 - 5 SIEMENS

12 Modbus 2-237 Chap.212.4 Environment Settings 12.4.1 Twido Items Details Serial Interface RS-232C/RS485-2wire Slave Address 1 – 247(DEC)

Strona 155 - 5.2.2 S7-300/400

Chapter2 Connection to a PLC 2-238 12.5 Usable Devices 12.5.1 Modbus RTU Master, MODBUS/TCP Client, MODBUS/TCP Server ・ Bit Device Device Symbol D

Strona 156 - 330-Ohm

12 Modbus 2-239 Chap.212.4.3 Momentum (MODBUS/TCP Client) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gra

Strona 157 - 2-157

Chapter 2 Connection to a PLC 2-24 1.2.11 OpenNet Controller/MICROSmart/MICROSmart Pentra ( uses Web Server Unit ) MICRO/I FC3A FC4A FC5A Web Serv

Strona 158 - 5.4.1 S7-200

Chapter2 Connection to a PLC 2-240 12.6 MODBUS/TCP Server 12.6.1 Overview of the MODBUS/TCP Server Communication 12.6.1.1 Overview The MODBUS/TCP S

Strona 159 - 5.4.2 S7-300/S7-400

12 Modbus 2-241 Chap.212.6.2 System Configuration The following is the system configuration. - Up to 4 host devices can com

Strona 160 - 5.5.1 S7-200

Chapter2 Connection to a PLC 2-242 12.6.4 Devices The following devices are available for MODBUS/TCP Server communication. Bit Device Device Name

Strona 161 - 2-161

12 Modbus 2-243 Chap.212.6.5 Settings The settings of the MODBUS/TCP Server communication can be configured in the [Select Host Port] and [Proj

Strona 162 - 5.5.2 S7-300/S7-400

Chapter2 Connection to a PLC 2-244 12.6.6 Communication Format This chapter describes the communication format of the MODBUS/TCP Server communicati

Strona 163 - 6 Keyence

12 Modbus 2-245 Chap.212.6.6.2 Basic Format The following table lists the basic format of communications. The same format applies to both reques

Strona 164 - 6.2 System Configuration

Chapter2 Connection to a PLC 2-246 12.6.6.3 Reference Numbers Reference numbers are used to specify a device address with the MODBUS/TCP. The refe

Strona 165 - KV Series

12 Modbus 2-247 Chap.212.6.6.4 Functions The MICRO/I supports the following functions. Function code Function name Description 3 Read multiple

Strona 166 - 6.3 Connection Diagram

Chapter2 Connection to a PLC 2-248 FC16 Write multiple registers Writing to Holding Register (HR) consecutively (Request) Byte 7 FC (Function cod

Strona 167

12 Modbus 2-249 Chap.2FC1 Read coils Reading of Coil (C) consecutively (Request) Byte 7 FC (Function code) = 01 Byte 8-9 Reference No. Byte 1

Strona 168

1 IDEC 2-25 Chap.21.2.12 1: N Communication-OpenNet Controller/MICROSmart/MICROSmart Pentra The 1: N communication can be established by using t

Strona 169

Chapter2 Connection to a PLC 2-250 FC2 Read discrete inputs Reading of Input Relay (I) consecutively (Request) Byte 7 FC (Function code)=02 Byt

Strona 170 - 6.4 Environment Settings

12 Modbus 2-251 Chap.2FC4 Read input registers Reading of Input Register (IR) consecutively (Request) Byte 7 FC (Function code)=04 Byte 8-9 R

Strona 171 - 2-171

Chapter2 Connection to a PLC 2-252 FC5 Write coil Writing to a single Coil (C) (Request) Byte 7 FC (Function code)=05 Byte 8-9 Reference No. Byt

Strona 172 - 6.5.1 KV-700/1000

12 Modbus 2-253 Chap.2FC6 Write single register Writing to a single Holding Register (HR) (Request) Byte 7 FC (Function code) = 06 (HEX) Byte

Strona 173 - 2-173

Chapter2 Connection to a PLC 2-254 FC7 Read exception status Reading of exception status (Bit 0 to 7 of HR400001) (Request) Byte 7 FC (Function c

Strona 174

13 Panasonic(AROMAT) 2-255 Chap.213 Panasonic(AROMAT) 13.1 Connection Table 13.1.1 Compatible PLCs WindO/I-NV2 Setting Name ManufacturerSeries N

Strona 175 - 7.SHARP

Chapter2 Connection to a PLC 2-256 WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit Interface Flow Control Host I/F Dr

Strona 176 - 7.2 System Configuration

13 Panasonic(AROMAT) 2-257 Chap.213.2 System Configuration This is the system configuration for connection of Panasonic(AROMAT) PLCs to the MIC

Strona 177 - 2-177

Chapter2 Connection to a PLC 2-258 C32T,C24R2,C32T2 RS-232C Connection Diagram 13-6C32T,C24R2,C32T2 RS-485 Connection

Strona 178 - 7.2.6 JW10 Series

13 Panasonic(AROMAT) 2-259 Chap.2 RS-232CConnection Diagram 13-8MICRO/I TOOL COM Power FP2, FP2SH FP10, FP10SH RS-232C Connection Diagram 13

Strona 179

Chapter 2 Connection to a PLC 2-26 1.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cable

Strona 180

Chapter2 Connection to a PLC 2-260 13.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not for th

Strona 181

13 Panasonic(AROMAT) 2-261 Chap.2Connection Diagram 13-3: FP1 (AFP8550)-MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No. Nam

Strona 182

Chapter2 Connection to a PLC 2-262 Connection Diagram 13-4 : FP1-MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pin No. Name

Strona 183

13 Panasonic(AROMAT) 2-263 Chap.2Connection Diagram 13-5: FPΣ- Communication cassette (AFPG801)-MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C

Strona 184

Chapter2 Connection to a PLC 2-264 Connection Diagram 13-7: FPΣ- Communication cassette (AFPG803)-MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-48

Strona 185 - 7.4 Environment Settings

13 Panasonic(AROMAT) 2-265 Chap.2Connection Diagram 13-8: FP2, FP2SH, FP10, FP10SH - MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No.

Strona 186

Chapter2 Connection to a PLC 2-266 13.4 Environment Settings 13.4.1 AROMAT FP series 13.4.1.1 FP0 and FP1 (tool port on CPU unit). Items Details S

Strona 187 - 7.5 Usable Devices

13 Panasonic(AROMAT) 2-267 Chap.213.4.1.4 FP10 and FP10SH (tool port on CPU unit). Items Details Serial Interface RS-232C Slave Address 1 – 3

Strona 188

Chapter2 Connection to a PLC 2-268 13.4.1.7 PLC FP2 and FP2SH (Computer Communication Unit) Items Details Serial Interface RS-232C Slave Address

Strona 189 - 8 Hitachi

13 Panasonic(AROMAT) 2-269 Chap.213.5 Usable Devices Types of devices supported by the MICRO/I and their ranges are shown below. ・ Bit Device

Strona 190 - 8.2 System Configuration

1 IDEC 2-27 Chap.2Connection Diagram 1-2: FA-3S (PF3S-SIF4) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pin No. Name

Strona 191 - 2-191

Chapter2 Connection to a PLC 2-270 14 YASKAWA 14.1 Connection Table 14.1.1 Compatible Motion Controllers Manufacturer Series Name System (CPU unit

Strona 192

14 YASKAWA 2-271 Chap.214.2 System Configuration This is the system configuration for connection of YASKAWA ELECTRIC CORPORATION PLCs to the MIC

Strona 193 - 2-193

Chapter2 Connection to a PLC 2-272 14.2.3 MP2300(217IF-01) MICRO/I MP2300 217IF-01RS-232CConnection Diagram 14-1RS-485Connection Diagram 14-4RS-42

Strona 194 - 8.4.1 S10mini, S10V

14 YASKAWA 2-273 Chap.214.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cable. For de

Strona 195 - 8.5 Usable Devices

Chapter2 Connection to a PLC 2-274 Connection Diagram 14-2:MP920,MP930(217IF) - MICRO/I(RS-422) PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422)

Strona 196 - DW 0-15 DW 0-0

14 YASKAWA 2-275 Chap.2Connection Diagram 14-3:MP920,MP930(217IF) - MICRO/I(RS-485) PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No.

Strona 197 - 2-197

Chapter2 Connection to a PLC 2-276 Connection Diagram 14-4:MP22300(217IF-01) - MICRO/I(RS-422) PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) P

Strona 198 - 9 JTEKT(Toyoda)

14 YASKAWA 2-277 Chap.2Connection Diagram 14-5:MP2300(217IF-01) - MICRO/I(RS-485) PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. P

Strona 199 - 9.2 System Configuration

Chapter2 Connection to a PLC 2-278 14.4 Environment Settings 14.4.1 MP920, MP930, MP2300 Items Details Serial Interface RS-232C Protocol MEMOBUS

Strona 200

14 YASKAWA 2-279 Chap.214.5 Usable Devices ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Coil MB M

Strona 201

Chapter 2 Connection to a PLC 2-28 Connection Diagram 1-3: FA-3S, FA-2J (PF2-CLA) to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No.

Strona 202 - 9.4.1 TOYOPUC-PC3J Series

Chapter2 Connection to a PLC 2-280 15 Koyo Selecting DirectLogic DL205/205 or DirectLogic(Ethernet) for the Host I/F Driver allows the user to use

Strona 203 - 9.5.1 TOYOPUC-PC3J

15 Koyo 2-281 Chap.215.2 System Configuration This is the system configuration for connection of Koyo PLCs to the MICRO/I. 15.2.1 DirectLogi

Strona 204

Chapter2 Connection to a PLC 2-282 15.2.4 DirectLogic 205 (connects to CPU unit RS-232C port) D2-240 MICRO/I Connection Diagram 15-3RS-232C 1

Strona 205 - 2-205

15 Koyo 2-283 Chap.215.2.6 DirectLOGIC Series (Ethernet) DirectLOGIC 05DirectLOGIC 06 MICRO/I EthernetDirectLOGIC 205 DirectLOGIC 405 D0-ECOMD

Strona 206

Chapter2 Connection to a PLC 2-284 15.3 Connection Diagram For details regarding wiring and termination resistors, refer to "3 Important Poi

Strona 207 - 10 Toshiba Machine Works

15 Koyo 2-285 Chap.2Connection Diagram 15-2: D4-440(CPU unit RS-422 port) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No.

Strona 208 - TC3-13B1

Chapter2 Connection to a PLC 2-286 Connection Diagram 15-3: D2-240(CPU unit RS-232C port) to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin

Strona 209 - TCmini (RS-232C) - MICRO/I

15 Koyo 2-287 Chap.215.4 Environment Settings 15.4.1 D4-440 CPU Unit Communication port Items Details Serial Interface RS-232C / RS-422 Data r

Strona 210

Chapter2 Connection to a PLC 2-288 15.4.4 Ethernet Unit on DirectLOGIC Set following Items in Project Settings Dialog. Item Setting IP Address (

Strona 211 - 10.4.1 TC200

15 Koyo 2-289 Chap.215.5 Usable Devices 15.5.1 DL405 ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual I

Strona 212 - 10.5 Usable Devices

1 IDEC 2-29 Chap.2Connection Diagram 1-4: MICRO3 (loader port) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pin No. N

Strona 213 - 11 GE Fanuc Automation

Chapter2 Connection to a PLC 2-290 ・ Word Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Input Points (Word) XW

Strona 214 - 11.2 System Configuration

15 Koyo 2-291 Chap.215.5.2 DL205 ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Input Points (Bit) X

Strona 215 - (CMM) (RS-232C) to MICRO/I

Chapter2 Connection to a PLC 2-292 ・ Word Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Input Points (Word) XW

Strona 216

15 Koyo 2-293 Chap.215.5.3 DirectLOGIC,KOSTAC-SU(Ethernet) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gra

Strona 217

Chapter2 Connection to a PLC 2-294 ・ Word Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Input Points(Word) VX

Strona 218

16 FANUC 2-295 Chap.216 FANUC 16.1 Connection Table 16.1.1 Compatible PLCs Manufacturer Series Name System (CPU unit) Link Unit WindO/I-NV2 Se

Strona 219 - 11.4 Environment Settings

Chapter2 Connection to a PLC 2-296 16.2 System Configuration This is the system configuration for connection of FANUC PLCs to the MICRO/I. 16.2.1

Strona 220 - 11.4.3 VersaMax Micro/Nano

16 FANUC 2-297 Chap.216.3 Connection Diagram For details regarding wiring and termination resistors, refer to "3 Important Points Regardi

Strona 221 - 11.5 Usable Devices

Chapter2 Connection to a PLC 2-298 Connection Diagram 16-2: Series 16i,160i,18i,180i,30i,31i,32i to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-23

Strona 222

16 FANUC 2-299 Chap.216.4 Environment Settings 16.4.1 Power Mate-MODEL D Items Details Serial Interface RS422-4wire Slave Address 0(Fixed) Ba

Strona 223 - 12 Modbus

2-3 Chap.22.4.1 MELSEC-A Series: Settings for the Computer Link Unit and CPU Unit Link I/F...

Strona 224 - 12.1.2 Compatible PLCs

Chapter 2 Connection to a PLC 2-30 Connection Diagram 1-5: MICRO3C (Loader port) to MICRO/I OpenNet Controller (RS-232C port) to MICRO/I MICROSmart

Strona 225 - 2-225

Chapter2 Connection to a PLC 2-300 16.5 Usable Devices 16.5.1 Power Mate-MODEL D, Series 16i,160i,18i,180i,30i,31i,32i ・ Bit Device Device Symbol

Strona 226 - Manufacturer

17 YOKOGAWA 2-301 Chap.217 YOKOGAWA 17.1 Connection Table 17.1.1 Compatible PLCs Manufacturer Series Name System (CPU unit) Link Unit WindO/I-

Strona 227 - 12.2.3 Modbus/TCP Server

Chapter2 Connection to a PLC 2-302 17.2 System Configuration This is the system configuration for connection of YOKOGAWA PLCs to the MICRO/I. 17.2.

Strona 228 - 12.2.4 Twido

17 YOKOGAWA 2-303 Chap.217.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cable. For d

Strona 229 - 2-229

Chapter2 Connection to a PLC 2-304 Connection Diagram 17-2: FA-M3 F3LC11-2N - MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin

Strona 230

17 YOKOGAWA 2-305 Chap.2Connection Diagram 17-3: FA-M3 - MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No. Name Name

Strona 231 - 2-231

Chapter2 Connection to a PLC 2-306 17.4 Environment Settings 17.4.1 YOKOGAWA FA-M3 YOKOGAWA FA-M3 - Link Unit (F3LC11-1N, F3LC112N) to MICRO/I Sett

Strona 232 - 171CCC9602

17 YOKOGAWA 2-307 Chap.217.5 Usable Devices ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Input Rel

Strona 233 - 2-233

Chapter2 Connection to a PLC 2-308 7 16 64(0 – 7) (2 – 16) (1 – 64) (*2) Please specify in the following ranges. 7 8192 (0 – 7)

Strona 234 - 12.3 Connection Diagram

18 INVERTER 2-309 Chap.218 INVERTER 18.1 Connection Table 18.1.1 Compatible Mitsubishi Inverters WindO/I-NV2 Setting Name ManufacturerSeries Na

Strona 235

1 IDEC 2-31 Chap.2Connection Diagram 1-6: MICRO3C (Data Link port) to MICRO/I OpenNet Controller (RS-485 port) to MICRO/I MICROSmart/MICROSmart

Strona 236

Chapter2 Connection to a PLC 2-310 18.2 System Configuration The following is the system configuration for connecting a Mitsubishi inverter with th

Strona 237 - 12.4.1 Twido

18 INVERTER 2-311 Chap.218.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cable. Conn

Strona 238 - 12.5 Usable Devices

Chapter2 Connection to a PLC 2-312 18.4 Environment Settings The following shows the settings of the communication port for performing communicatio

Strona 239 - 2-239

18 INVERTER 2-313 Chap.218.5 Usable Devices ・ Word Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Parameter

Strona 240 - 12.6.1.1 Overview

Chapter2 Connection to a PLC 2-314 (*2) This device is handled as a 32-bit device by combining addresses 0 and 1. (*3) The Link parameter expansi

Strona 241 - 12.6.3 Wiring

19 FUJI 2-315 Chap.219 FUJI 19.1 Connection Table 19.1.1 Compatible PLCs WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Li

Strona 242 - 12.6.4 Devices

Chapter2 Connection to a PLC 2-316 WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit Interface Flow Control Host I/F Dr

Strona 243 - 12.6.5 Settings

19 FUJI 2-317 Chap.219.2 System Configuration This is the system configuration for connection of FUJI PLCs to the MICRO/I. 19.2.1 FLEX-PC Serie

Strona 244 - 12.6.6 Communication Format

Chapter2 Connection to a PLC 2-318 NJ Series RS-232CConnection Diagram 19-3RS-485Connection Diagram 19-4FREX-PC-NJ MICRO/I MICRO/I NJ-RS2 NJ-RS4

Strona 245 - 12.6.6.2 Basic Format

19 FUJI 2-319 Chap.219.2.3 MICREX-F Series (Interface Card) F55 MICREX-F F55 NV1L-RS2 RS-232C Connection Diagram19-5 MICRO/I F70 MIC

Strona 246 - 12.6.6.3 Reference Numbers

Chapter 2 Connection to a PLC 2-32 Connection Diagram 1-7: MICROSmart/MICROSmart Pentra (RS-232C Port 1) to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F

Strona 247 - 12.6.6.4 Functions

Chapter2 Connection to a PLC 2-320 19.2.4 MICREX-F Series (Interface Module) F30/F50/F50H/F55/F60/F70/F70S/F80H/F81/F120H/F120S/F140S/F150S RS-23

Strona 248

19 FUJI 2-321 Chap.219.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cable. For detai

Strona 249 - FC1 Read coils

Chapter2 Connection to a PLC 2-322 PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No. Name Name HG1FConnectorHG2F/3F/4FHG2S 1 FG FG

Strona 250 - FC2 Read discrete inputs

19 FUJI 2-323 Chap.2PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pin No. Name Name HG1FConnectorHG1FTerminalHG2F/ 3F/4F HG2S -

Strona 251 - FC4 Read input registers

Chapter2 Connection to a PLC 2-324 Connection Diagram 19-6:MICREX-F Series(RS-458 Port)- MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422)

Strona 252 - FC5 Write coil

19 FUJI 2-325 Chap.219.4 Environment Settings 19.4.1 FUJI FLEX-PC (CPU) 19.4.1 FUJI FLEX-PC (CPU) to MICRO/I Setting Items Details Serial Inter

Strona 253 - FC6 Write single register

Chapter2 Connection to a PLC 2-326 FLEX-PC Communication Setting When you would like to set up the communication setting with the initialization

Strona 254 - 12.5.6.5 Exception code

19 FUJI 2-327 Chap.221.4.3 FUJI MICREX-F Interface Card/Module Items Details Serial Interface RS-232C RS-485 (4wire) Operation Modes (*1) C

Strona 255 - 13 Panasonic(AROMAT)

Chapter2 Connection to a PLC 2-328 19.5 Usable Devices 19.5.1 FREX-PC ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddre

Strona 256 - Panasonic(AROMAT)

19 FUJI 2-329 Chap.219.5.2 MICREX-F ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual In.Output Relay(bit

Strona 257 - 13.2.1 AROMAT

1 IDEC 2-33 Chap.2Connection Diagram 1-8: MICROSmart/MICROSmart Pentra (FC5A-SIF2) to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No.

Strona 258 - AFPG801

Chapter2 Connection to a PLC 2-330 ・ Word Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual InOut Relay(word) WB

Strona 259 - 2-259

20 Toshiba 2-331 Chap.220 Toshiba 20.1 Connection Table 20.1.1 Compatible PLCs WindO/I-NV2 Setting Name ManufacturerSeries Name System (CPU uni

Strona 260 - 13.3 Connection Diagram

Chapter2 Connection to a PLC 2-332 WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit InterfaceFlow Control Host I/F Dri

Strona 261 - 2-261

20 Toshiba 2-333 Chap.220.2 System Configuration This is the system configuration for connection of Toshiba PLCs to the MICRO/I. 20.2.1 PROSEC

Strona 262

Chapter2 Connection to a PLC 2-334 20.2.3 PROSEC T Series T2 (PU224) RS-485Connection Diagram 20-1 T2(PU224) MICRO/I 20.2.4 PROSEC T Series T2E R

Strona 263 - 2-263

20 Toshiba 2-335 Chap.220.2.5 PROSEC T Series T2N RS-232CConnection Diagram 20-2 RS-485Connection Diagram 20 -7 T2NMICRO/I MICRO/I RS-232CConnec

Strona 264

Chapter2 Connection to a PLC 2-336 20.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cabl

Strona 265 - 2-265

20 Toshiba 2-337 Chap.2Connection Diagram 20-2: RS-232 D-sub 9P - MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No. Name Na

Strona 266 - 13.4.1 AROMAT FP series

Chapter2 Connection to a PLC 2-338 Connection Diagram 20-4:T1,T1S RS-232C Din connector 8P - MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pi

Strona 267 - 2-267

20 Toshiba 2-339 Chap.2Connection Diagram 20-6:T2N RS-232C D-sub 15Pin connector(RS232C/RS485) - MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C

Strona 268 - Items Details

Chapter 2 Connection to a PLC 2-34 1.4 Environment Settings 1.4.1 FA-3S Series (Serial Interface Unit) Item Setting Communication Device Number 0

Strona 269 - 13.5 Usable Devices

Chapter2 Connection to a PLC 2-340 20.4 Environment Settings Refer to the followings to configure the communication port between PLC (PROSEC T Ser

Strona 270 - 14 YASKAWA

20 Toshiba 2-341 Chap.220.5 Usable Devices ・Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Input device

Strona 271 - 2-271

Chapter2 Connection to a PLC 2-342 20.6 The mapping table of devices between PROSEC T Series and V Series When you use V Series PLCs, refer to the

Strona 272 - 217IF-01

21 LS Industrial Systems 2-343 Chap.221 LS Industrial Systems 21.1 Connection Table 21.1.1 Compatible PLCs WindO/I-NV2 Setting Name Manufacture

Strona 273 - 14.3 Connection Diagram

Chapter2 Connection to a PLC 2-344 21.2 System Configuration This is the system configuration for connection of LS Industrial Systems PLCs to the M

Strona 274

21 LS Industrial Systems 2-345 Chap.221.2.4 MASTER-K K200S (Interface Module) MASTER-K K200S G6L-CUEB RS-232CConnection Diagram 21-3 RS-485(4 wi

Strona 275

Chapter2 Connection to a PLC 2-346 21.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cabl

Strona 276

21 LS Industrial Systems 2-347 Chap.2Connection Diagram 21-3: MASTER-K (Interface Module RS232C Port) - MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(

Strona 277

Chapter2 Connection to a PLC 2-348 21.4 Environment Settings Refer to the followings to configure the communication port between PLC (PROSEC T Ser

Strona 278 - 14.4.1 MP920, MP930, MP2300

21 LS Industrial Systems 2-349 Chap.221.5 Usable Devices ・Bit Device Device Symbol Device Name HG PLC Address RangeRead /Write Address Gradual

Strona 279 - 14.5 Usable Devices

1 IDEC 2-35 Chap.21.4.2 FA-3S and FA-2J (Ring Adapter) Item Setting Baud Rate (bps) 9600 Data Bits (bits) 8 Parity Even Stop Bits 1 Devic

Strona 280 - 15 Koyo

Chapter 2 Connection to a PLC 2-36 1.4.4 OpenNet Controller,MICROSmart/MICROSmart Pentra ( uses Web Server Unit ) Set following Items in Project Se

Strona 281 - RS-232C port)

1 IDEC 2-37 Chap.21.5 Usable Devices 1.5.1 FA-3S (CP11, CP11T), FA2J ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write A

Strona 282 - Diagram 15-3

Chapter 2 Connection to a PLC 2-38 1.5.2 FA-3S (CP12, CP13) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual

Strona 283 - 15 Koyo

1 IDEC 2-39 Chap.21.5.3 MICRO3/MICRO3C ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Internal Relay

Strona 284 - 15.3 Connection Diagram

Chapter 2 Connection to a PLC 2-4 3.4.1 PLC Link Unit Settings...2

Strona 285

Chapter 2 Connection to a PLC 2-40 1.5.4 OpenNet Controller/MICROSmart (uses Web Server Unit) ・ Bit Device Device Symbol Device Name HG PLC Addr

Strona 286

2 Mitsubishi 2-41 Chap.22 Mitsubishi Selecting MELSEC-Q (CPU), MELSEC-FX (CPU), MELSEC-FX2N (CPU), or MELSEC-FX3U (CPU) for the Host I/F Driver

Strona 287 - 15.4.2 D4-DCM

Chapter 2 Connection to a PLC 2-42 RS-232C (Connection Diagram 2-3) A2US,A2USH-S1 A1SJ71C24-R2 A1SJ71UC24-R2A1SJ71C24-R4 A1SJ71UC24-R2RS-485 (422)-

Strona 288

2 Mitsubishi 2-43 Chap.2WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit Interface Flow Control Host I/F Driver AJ7

Strona 289 - 15.5.1 DL405

Chapter 2 Connection to a PLC 2-44 WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit Interface Flow Control Host I/F Dr

Strona 290

2 Mitsubishi 2-45 Chap.2WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit Interface Flow Control Host I/F Driver FX0

Strona 291 - 15.5.2 DL205

Chapter 2 Connection to a PLC 2-46 2.2 System Configuration This is the system configuration for connection of Mitsubishi PLCs to the MICRO/I. 2.2

Strona 292

2 Mitsubishi 2-47 Chap.22.2.2 MELSEC-A Series (connected to the CPU Unit Link I/F) MICRO/I RS-232C (Connection Diagram 2-3)A2CCPU24 In cas

Strona 293

Chapter 2 Connection to a PLC 2-48 2.2.4 MELSEC-Q/QnA Series (using the Computer Link Unit) MICRO/I RS-485 Connection Diagram 2-2 RS-232C Connecti

Strona 294 - Word Device

2 Mitsubishi 2-49 Chap.2 MICRO/IRS-485 Connection Diagram 2-2 RS-232C Connection Diagram 2-3 Q2ASH PU-S1 Q2ASHCPU Q2ASCPU-S1 Q2ASCPU A1SJ71QC24N

Strona 295 - 16 FANUC

2-5 Chap.24.5.1 MicroLogix, SLC 500 (Full Duplex)...2-127 4.5.2 SLC 500 (Half Dupl

Strona 296 - 16.2.1 Power Mate-MODEL D

Chapter 2 Connection to a PLC 2-50 2.2.6 MELSEC-FX Series (connects to the CPU unit programming port) RS-422 (Connection Diagram 2-4)MICRO/IFX1,

Strona 297

2 Mitsubishi 2-51 Chap.2 In case of HG2F/3F/4F a connection cable is available for Connection Diagram 2-4 (part number: HG9Z-3C165). In case

Strona 298

Chapter 2 Connection to a PLC 2-52 MICRO/I RS-485 (Connection Diagram 2-2)FX1N-485-BDFX1N FX2N-485-BDFX2N 2.2.7 MELSEC-FX Series (connects to F

Strona 299 - 16.4.1 Power Mate-MODEL D

2 Mitsubishi 2-53 Chap.22.2.8 MELSEC-Q/QnA Series (Using the Ethernet Unit) MICRO/I Ethernet(TCP/IP) Q00JCPU, Q00CPU Q01CPU, Q02CPU Q02HCPU, Q

Strona 300 - 16.5 Usable Devices

Chapter 2 Connection to a PLC 2-54 2.3 Connection Diagram The connector types given in the Connection Diagrams are for the unit and not the cable

Strona 301 - 17 YOKOGAWA

2 Mitsubishi 2-55 Chap.2Connection Diagram 2-2: Computer Link Unit (RS-485) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No

Strona 302 - 17.2.1 YOKOGAWA

Chapter 2 Connection to a PLC 2-56 Connection Diagram 2-3: Computer Link Unit (RS-232C) to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin N

Strona 303 - MICRO/I

2 Mitsubishi 2-57 Chap.2Connection Diagram 2-4: PLC, 2-port Adapter to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pin

Strona 304

Chapter 2 Connection to a PLC 2-58 Connection Diagram 2-5: FX2N-232-BD to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No. Name

Strona 305

2 Mitsubishi 2-59 Chap.2Connection Diagram 2-7: MELSEC-Q(CPU unit programming port )to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin N

Strona 306 - 17.4.1 YOKOGAWA FA-M3

Chapter 2 Connection to a PLC 2-6 Connection Diagram 6-3: KV-700/1000 + KV-20R (PORT2-RS-232C) to MICRO/I...

Strona 307 - 17.5 Usable Devices

Chapter 2 Connection to a PLC 2-60 Connection Diagram 2-8: FX2NC-232ADP/FX3U-232ADP - MICRO/I to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C)

Strona 308

2 Mitsubishi 2-61 Chap.2Connection Diagram 2-9: Computer Link Unit (RS-485) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No.

Strona 309 - 18 INVERTER

Chapter 2 Connection to a PLC 2-62 Connection Diagram 2-10: MELSEC-FX Series CPU (RS-485) to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422)

Strona 310 - 18.2.1 Mitsubishi

2 Mitsubishi 2-63 Chap.22.4 Environment Settings 2.4.1 MELSEC-A Series: Settings for the Computer Link Unit and CPU Unit Link I/F Setting Item R

Strona 311

Chapter 2 Connection to a PLC 2-64 2.4.2 MELSEC-A Series: Connection to the Programming Port or 2-port Adapter Item Setting Communication Interfac

Strona 312 - 18.4 Environment Settings

2 Mitsubishi 2-65 Chap.22.4.4 MELSEC-Q00, 01CPU: Connection to the Programming Port Please confirm by parameter setup of MELSEC-Q00 and 01CPU &q

Strona 313 - 18.5 Usable Devices

Chapter 2 Connection to a PLC 2-66 2.4.6 MELSEC-FX Series Item Setting Communication Interface RS-232C/RS-422 Data Bits 7 (fixed) Baud Rate 9

Strona 314

2 Mitsubishi 2-67 Chap.22.4.7 MELSEC-Q/QnA:In case using Ethernet Unit setting MICRO/I setting Item Setting IP Address Set IP Address to MIC

Strona 315 - 19 FUJI

Chapter 2 Connection to a PLC 2-68 PLC Settings Item setteing notes Network type Ethernet (*1) Starting I/O No. 0020 (*2) NetworkNo. 1 (*2

Strona 316

2 Mitsubishi 2-69 Chap.22.5 Usable Devices 2.5.1 MELSEC-AnA (LINK) Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Addres

Strona 317 - NB Series

2-7 Chap.28.2.1 S10mini (LQP000) (connect to CPU unit RS-232C port) ...2-190 8.2.2 S10mini Communication module...

Strona 318 - NS Series

Chapter 2 Connection to a PLC 2-70 2.5.1 MELSEC-AnN (LINK) Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Inp

Strona 319 - 19 FUJI

2 Mitsubishi 2-71 Chap.22.5.2 MELSEC-AnA (CPU) Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Input Rela

Strona 320

Chapter 2 Connection to a PLC 2-72 2.5.3 MELSEC-AnN (CPU) Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Inpu

Strona 321

2 Mitsubishi 2-73 Chap.22.5.4 MELSEC-AnU (CPU) Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Input Rela

Strona 322

Chapter 2 Connection to a PLC 2-74 2.5.5 MELSEC-A1S/A2C (CPU) Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual

Strona 323

2 Mitsubishi 2-75 Chap.2Word Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Input Relay WX X 0 - 1F0 R (

Strona 324

Chapter 2 Connection to a PLC 2-76 2.5.6 MELSEC-Q/QnA(Link) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradua

Strona 325

2 Mitsubishi 2-77 Chap.2・ Word Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Input Relay WX X 0 - 1FF0

Strona 326

Chapter 2 Connection to a PLC 2-78 2.5.7 MELSEC-Q (CPU) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Int

Strona 327

2 Mitsubishi 2-79 Chap.2・ Word Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Input Relay WX X 0 - 1FF0

Strona 328 - Bit Device

Chapter 2 Connection to a PLC 2-8 10.5 Usable Devices...

Strona 329 - 19.5.2 MICREX-F

Chapter 2 Connection to a PLC 2-80 2.5.8 MELSEC-FX (CPU) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual Inp

Strona 330

2 Mitsubishi 2-81 Chap.22.5.9 MELSEC-FX2N (CPU) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Input R

Strona 331 - 20 Toshiba

Chapter 2 Connection to a PLC 2-82 2.5.10 MELSEC-FX3UC (CPU) ・ Bit Device Device Symbol Device Name HG PLC Address Range Read/WriteAddress Gradual

Strona 332

2 Mitsubishi 2-83 Chap.22.5.11 MELSEC-Q/QnA(Ethernet) ・Bit Device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Sp

Strona 333 - 20.2.2 PROSEC T Series T1S

Chapter 2 Connection to a PLC 2-84 ・Word device Device Symbol Device Name HG PLC Address Range Read /Write Address Gradual Special Register SD S

Strona 334 - 20.2.4 PROSEC T Series T2E

3 Omron 2-85 Chap.23 Omron 3.1 Connection Table 3.1.1 Compatible PLCs WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link U

Strona 335 - 20.2.5 PROSEC T Series T2N

Chapter 2 Connection to a PLC 2-86 WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit Interface Flow Control Host I/F D

Strona 336

3 Omron 2-87 Chap.2WindO/I-NV2 Setting Name Manufacturer Series Name System (CPU unit) Link Unit Interface Flow Control Host I/F Driver CS1G,CS1

Strona 337 - 20 Toshiba

Chapter 2 Connection to a PLC 2-88 3.2 System Configuration This is the system configuration for connection of Omron PLCs to the MICRO/I 3.2.1 SYSM

Strona 338

3 Omron 2-89 Chap.2 C200HS C200H-LK201 C200H-LK202MICRO/I MICRO/I RS-232C (Connection Diagram 3-1) RS-422 (Connection Diagram 3-2) In case o

Strona 339 - 形(RS-485/422)

2-9 Chap.2Connection Diagram 12-3: TWDNAC485T to MICRO/I... 2-236 12.4 Environment Settings ...

Strona 340

Chapter 2 Connection to a PLC 2-90 C200Hα C200H-LK202-V1 MICRO/I MICRO/I C200HE, C200HG, C200HX C200H-LK201-V1 RS-232C (Connection Diagram 3-1) R

Strona 341

3 Omron 2-91 Chap.2 CS1W-SCB41(port1) CS1 Series CS1W-SCB41(port2) Communication Board MICRO/I MICRO/I RS-232C (Connection Diagram 3-6) Commu

Strona 342

Chapter 2 Connection to a PLC 2-92 3.2.2 SYSMAC-C Series (using the Link I/F on the CPU Unit) RS-232C (Connection Diagram 3-4) C20H,C28H,C40H and

Strona 343 - 21 LS Industrial Systems

3 Omron 2-93 Chap.2 RS-232C (Connection Diagram 3-5) CS1 Series MICRO/I In case of HG2F/3F/4F a connection cable is available for Connection

Strona 344 - 21.2 System Configuration

Chapter 2 Connection to a PLC 2-94 3.3 Connection Diagram For details regarding wiring, refer to "3 Important Points Regarding About Wiring&

Strona 345 - Connection Diagram 21-4

3 Omron 2-95 Chap.2Connection Diagram 3-2: RS-422 Link unit to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pin No. Name

Strona 346 - Chapter 1

Chapter 2 Connection to a PLC 2-96 Connection Diagram 3-3: RS-422 Link unit to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No.

Strona 347 - 21 LS Industrial Systems

3 Omron 2-97 Chap.2Connection Diagram 3-4: CPU Unit Link I/F to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No. Name Name

Strona 348

Chapter 2 Connection to a PLC 2-98 Connection Diagram 3-6: PLC (RS-232C) I/F to MICRO/I PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C) Pin No. Pin No

Strona 349 - 2-349

3 Omron 2-99 Chap.2Connection Diagram 3-7: RS-422 Communication Board to MICRO/I PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422) Pin No. Pi