Mitsubishi RS232/485/LAN Serial Communication Control Instrukcja Obsługi Strona 29

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 349
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 28
1 IDEC
2-29
Chap.2
Connection Diagram 1-4: MICRO3 (loader port) to MICRO/I
PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422)
Pin No.
Pin No.
Name
Name
HG1F
Connector
HG1F
Terminal
HG2F/
3F/4F
HG2S
Cover Shield FG Cover - 1 1
1 D+ TERM - - 9 -
2 D- RDA(RD+) 2 3 10 32
7 0V RDB(RD-) 7 4 16 33
SDA(SD+) 1 1 11 30
SDB(SD-) 6 2 15 31
CS- 9 - 18 37
RS- 8 - 19 35
CS+ 4 - 21 36
RS+ 3 - 22 34
SG 5 5 7 29
Internal
termination
resistor
330-Ohm
D-sub, 9P connector socket type (HG1F)
D-sub, 25P connector socket type (HG2F/3F/4F)
D-sub, 37P connector plug type (HG2S)
Mini DIN 8P
Shield Wire
- In case of HG2F/3F/4F a connection cable is available (part number: HG9Z-3C115).
- There is no pin No. corresponding to TERM on the HG1F/HG2S. When inserting a
termination resistor, use a communication switch. For the setting of the switch, refer to "3
Important Points Regarding Wiring" in Chapter 1.
When you use the Terminal Block type of HG1F, make sure to configure the Hardware Flow
control to NONE because the HG1F doesn’t have control lines.